Switch-ComPass Bs 2.0

The new ComPass with control function and freely programmable logic

Directional Short-Circuit and Directional Earth Fault Indicator with monitoring and control function

Product Features

  • For remote controlling of a load-break switch or circuit-breaker
  • Free assignment of 6 binary inputs for the collection and transmission of relevant switchgear/station data
  • Freely programmable logic for flexible definition of switchgear conditions
  • Directional short-circuit and directional earth fault indicator
  • Clear fault indication and reading on-site: 2 directional arrow LEDs (A, B) and high contrast OLED display
  • Monitoring of the parameters voltage (V), current (I), load flow
    direction (B↓ or A↑), power factor (cos φ), power (P, Q, S), energy (E), tem-perature (T) and frequency (f)
  • Suitable for all types of networks/neutral point treatments
  • Earth fault detection with 6 different earth fault detection methods, also in combination
  • High-precision current and voltage measurement to 0.5 %
  • Voltage monitoring with connection to capacitive and resistive (ohmic) sensors in one indicator
  • PT-100 temperature sensor for equipment monitoring
  • Limit monitoring: V, I, P, Q, T
  • ComPass Explorer Software: Commissioning and parametrisation via front accessible USB port

The Control ComPass Bs 2.0 is suitable for use in substations with a remote control connection of the electrical power distribution in a medium voltage network. In addition to the short-circuit and earth fault function,  ComPass B 2.0 supplies the collected measured values of current, voltage and power from the station for transmission to the control room. The PT100 sensor measures the temperature, for example of the transformer or the transformer station. For all measured values limits can be defined, which can also be transmitted to the control room.
The voltage coupling/measurement is done via the capacitive VDS system or via resistive (ohmic) voltage sensors. Up to four ComPass can be connected to one set of resistive voltage sensors.
In addition to the functions of the ComPass B 2.0, the Control ComPass Bs 2.0 offers a control function for switching a load-break switch or circuit-breaker. A free assignment of 6 binary inputs in combination with a freely programmable logic (PLC functionality) enables the user to define the switching conditions in a flexible manner. Random information, such as the SF6 gas disruption or HV tripped fuse, can be captured via the binary inputs.

Equipment set:

1 Display unit
3 single-phase current sensors
or 2 single and 1 summation current sensor

Product Video


Technical Data

Technical data

ComPass Bs 2.0

Detection of short-circuit and
earth fault direction

Earth fault detection methods Permanent, earth short-circuit, transient, cos φ and sin φ
Control system/freely programmable logic

Measured values / Indication

  • Phase currents I1, I2, I3, IE with phase angle

  • Phase-to-earth voltage V1, V2, V3, VNE and phase-to-phase voltage V12, V23, V31, VNE with phase angle

  • Load flow direction A↑ or B↓

  • P, Q, S and cos φ (power factor) (P1,2,3, Q 1,2,3, S 1,2,3, cos φ 1,2,3 via RS485)

  • Amount of active energy, separate for load flow direction A↑ or B↓; additionally per phase

  • Operating current, I1,2,3 ø15 min, Imax. 24 h/7 days/365 days,
    max. demand indicator I max. LR

  • Power frequency f

  • Temperature T

Measurement accuracy phase currents

Up to 0,5 % / 0,5 A depending on the type of sensor (split-core or closed bushing type)

Measurement accuracy voltages

Up to 0,5 % im Bereich 80 – 120 %/Un,depending on sensor type (resistive or capacitive)

I>> Short-circuit trip current

20 – 2,000 A; tI>> Response delay: 40 ms – 60 s

VNE> Permanent earth fault trip values

1 – 100 %; tUNE> Response delay: 40 ms – 60 s

IES> / IES>> Earth short-circuit trip current

10 – 1,000 A; tIES> / tIES>> Response delay: 40 ms – 60 s

IET> Transient method

1 – 500 A

IEP> Active current cos φ
/ IEQ> Reactive current sin φ

1 – 200 A ; tIEP> / tIQP> Response delay: 40 ms – 60 s

Limit monitoring
    I> Overload current
    U> Overvoltage
    U< Undervoltage
    P> / P>> Active power
    Q> / Q>> Reactive power
    T< / T<< / T> / T>> Temperature

 

5 – 1,500 A;tI> Response delay: 40 ms – 60 s
100 – 200 %; tU> Response delay: 40 ms – 60 s
1 – 100 %; tU< Response delay: 40 ms – 60 s
1 – 30,000 kW; tP> / tP>> Response delay: 40 ms – 60 s
1 – 30,000 kW; tQ> / tQ>> Response delay: 40 ms – 60 s
-40 °C bis +85 °C

Indication

LED fault direction and status indicators (multicolour); OLED display (multilingual)

Reset

  • Local, remote

  • Automatic time reset: 1 min – 24 h

  • Via RS485 / Modbus interface

  • Auxiliary supply restoration

  • Voltage restoration

  • Current restoration

  • ComPass Explorer Software

Remote signal / Communication

  • 4 potential-free, freely programmable relay contacts

  • RS485-/MODBUS interface

Parameter setting

USB port with ComPass Explorer Software

Remote contact

4 permanent or momentary contacts,
bistable, NC /NO
Contact capacity: 250 V AC/6 A; 30 V DC/
                             6 A, resistive load

Binary inputs

6, freely programmable, max. 30 V DC

Power supply

  • External auxiliary supply: 24 V – 230 V AC/DC (±10 %)

  • Internal power supply: Long-life lithium cell, shelf life ≥20 years, >1,000 h flashing time, >1.000 display activations

Housing

Polycarbonate, IP50

Temperature range

-30 to +70 °C

Accessories

Current Sensors

Single-phase current sensor

  • For new installation on bushings
  • For switchgear manufacturer
    • ORMAZABAL GA/GAE, GE
  • Ø 84 mm

Required order data:

For a set you need 3 single-phase current sensors.

more...
49-6025-311
Single-phase current sensor

  • For new installation on bushings
  • For switchgear manufacturer
    • Driescher type MINEX, MINEX C, G.I.S.E.L.A.
  • Ø 84 mm

Required order data:

  • For a set you need 3 single-phase current sensors.


*For screened connectors only. Insulation level: 0,72/3 kV

more...
49-6025-601*
Single-phase current sensor

  • For new installation on bushings
  • For switchgear manufacturer
    • Schneider Electric type FBX
  • Ø 84 mm


Required order data:

  • For a set you need 3 single-phase current sensors.

more...
49-6025-622
Single-phase current sensor

  • Split-core cable-type current sensor
  • For retrofit on insulated cables
  • For conductor 15 – 55 mm Ø
  • cable length 3 m

more...
49-6024-001

Wall-mounted Housings

Wall-mounted housing including earthing bar

  • 290 x 74 x 200 mm (W x H x D)

more...
V49-9001-007-001
Wall-mounted housing including earthing bar

  • 125 x 175 x 125 mm (W x H x D)

more...
V49-9001-004-001
Wall-mounted housing

  • 125 x 75 x 125 mm (W x H x D)

  • Bottom cable entry

more...
49-9001-001
Wall-mounted housing

  • 125 x 75 x 125 mm (W x H x D)

  • Rear cable entry

more...
49-9001-002

Other accessories for short-circuit and earth fault indicators

Disassembly clip

  • For retracting plug-in housings type Alpha, Opto, Earth  and Sigma

more...
49-9090-016
Spring clip

Spring clip suitable for 2 mm front plate thickness (standard)

more...
49-9090-018
Spring clip

Spring clip suitable for 3 mm front plate thickness

more...
49-9090-019

WEGA 1.2 C vario

WEGA 1.2 C vario

more...
51-1300-001

WEGA 1.2 C

WEGA 1.2 C

base type without C2

more...
51-1250-001

WEGA 2.2 C

WEGA 2.2 C

more...
51-2250-001

Dimensioned Drawings

Product

Note Item Number

ComPass Bs 2.0

Item Number38-4153-001


back to overview

Contact

Watch list