Voltage detecting systems

Notice | Product discontinuation of the Wega series according to IEC 61243-5

Please take note of the current information regarding the discontinuation.

If you need assistance in selecting alternative products, our field sales representatives and partners are at your disposal.

Wega 2.2 C

Integrated voltage detecting system with display and remote signalling

Wega 2.2 C is a 3-phase voltage detecting system, which indicates the following operating voltage states:

Additional to the LCD display the Wega 2.2 C has two LEDs (green U=0 and red U≠0). With two relay contacts the voltage state can be remotely monitored.

The built-in display test function at the front enables verification of the display of the installed and de-energised Wega 2.2 C.

For connection, either shielded or unshielded cables with flat connectors or system connectors can be used.

  • Designed according to IEC 61243-5 (VDE 0682-415)
  • Remote: two relay contacts
  • Wide-range Wega (e.g. 10 – 20 / 24 kV): Reduction of variants
  • Integrated maintenance test: maintenance-free
  • Retrofit ready: connection to ComPass B and Sigma D series
  • Front accessible LRM interface: fully featured according to IEC 61243-5
  • Fully enclosed electronics: high functional reliability
  • Overvoltage indication: phase-selective

Technical specifications

1-phase VDIS according to IEC 62271-213 -
2-phase VDIS according to IEC 62271-213 -
3-phase VDIS according to IEC 62271-213 -
3-phase VDS according to IEC 61243-5 ---
Capacitive voltage coupling for ComPass B series and Sigma D series ---
Overvoltage indication ---
Integrated permanent maintenance test ---
Adjustable C2 capacitor -
Assembly set for retrofit -
Nominal voltage 1 – 52 kV (nominal voltage of switchgear, further values on request)
Nominal frequency 50 – 60 Hz
Interfaces

3 LRM measuring sockets (one per phase) and 1 earth socket

LRM system, 14 mm distance between sockets, with captive anti-dust cap

Indication

LCD display with arrow, dot and wrench tool

LED indication U = 0 and U ≠ 0

Relay contacts 2 alternating relays contacts
Internal power supply

LCD display: fed by measuring voltage

External auxiliary supply -
CT powered -
Housing

Polycarbonate, IP54

Temperature range -25 to +65 °C
Cable diameter -
  1. Two bright LEDs for additional voltage indication
  2. Integrated phase-selective voltage indication
  3. Fully featured LRM interface (IEC61243-5)
  4. Two separate changeover relays for reporting the voltage states
  5. Wide-range input: 24 – 230 V AC/DC
  6. Various connection options