Notice | Product discontinuation of the Wega series according to IEC 61243-5
Please take note of the current information regarding the discontinuation.
If you need assistance in selecting alternative products, our field sales representatives and partners are at your disposal.
Wega 1.2 C
Wega 1.2 C is a 3-phase voltage detecting system, which indicates the following operating voltage states:
The built-in display test function at the front enables verification of the display of the installed and de-energised unit.
For connection, either shielded or unshielded cables with flat connectors or system connectors can be used.
- Designed according to IEC 61243-5 (VDE 0682-415)
- Wide-range Wega (e.g. 10 – 20 / 24 kV): Reduction of variants
- Integrated maintenance test: maintenance-free
- Retrofit ready: connection to ComPass B and Sigma D series
- Front accessible LRM interface: fully featured according to IEC 61243-5
- Fully enclosed electronics: high functional reliability
- Overvoltage indication: phase-selective
Technical specifications
1-phase VDIS according to IEC 62271-213 | - |
---|---|
2-phase VDIS according to IEC 62271-213 | - |
3-phase VDIS according to IEC 62271-213 | - |
3-phase VDS according to IEC 61243-5 | --- |
Capacitive voltage coupling for ComPass B series and Sigma D series | --- |
Overvoltage indication | --- |
Integrated permanent maintenance test | --- |
Adjustable C2 capacitor | - |
Assembly set for retrofit | - |
Nominal voltage | 1 – 52 kV (nominal voltage of switchgear, further values on request) |
Nominal frequency | 50 – 60 Hz |
Interfaces | 3 LRM measuring sockets (one per phase) and 1 earth socket LRM system, 14 mm distance between sockets, with captive anti-dust cap |
Indication | LCD display with arrow, dot and wrench tool |
Relay contacts | - |
Internal power supply | LCD display: fed by measuring voltage |
External auxiliary supply | - |
CT powered | - |
Housing | Polycarbonate, IP54 |
Temperature range | -25 to +65 °C |
Cable diameter | - |
- Integrated phase-selective voltage indication
- Fully featured LRM interface (IEC61243-5) to use with Orion 3.1 / M1
- Display test button
- Variable connection options (flat connectors & system connectors)
- Fully enclosed – high functional reliability
- Low installation depth: 26 mm