Voltage detectors

BO-A AC/DC

The new DC voltage detector for railway overhead lines

The BO-A AC/DC is a two-pole voltage detector for overhead lines of e.g. trams and electric buses. It is used to ensure the absence of voltage during maintenance work. The voltage detector BO-A AC/DC is suitable for use in DC and AC voltage networks.

When the BO-A AC/DC is connected to a live line, an optical and acoustic signal is activated. A DC or AC voltage network is detected and indicated automatically.

The BO-A AC/DC is designed and tested according to the standards IEC 61243-1,-2 and DIN VDE 0681-6. It can therefore be used worldwide.

According to DGUV regulation 3 (table 1c), the device should undergo a maintenance test every 6 years.

  • One device for DC and AC networks
  • Plug-in system – easy and quick to use
  • Integrated self-test device – increased safety
  • AC/DC-Residual Voltage Indicator
  • DC ± Polarity Indicator
  • Low weight – easy handling and transport
  • Use even in precipitation
  • Up to max. 4.7 m length – voltage testing from the ground
  • Magnetic earthing contact

Technical specifications

Dry conditions ---
Dry and wet conditions ---
Indication

„Standby“: green LED (after successful self-test)

„Voltage present“: red LED and acoustic signal

for DC with static polarity indication (blue/red)

for AC without polarity indication

„Voltage not present“: green LED, no acoustic signal

AC/DC residual voltage indicator: yellow flashing LED for:

AC residual voltage detection from 50 V RMS or DC residual voltage detection from ±75V

DC ± Polarity indicator: Detecting DC voltage polarity: red or blue flashing LED

Indication "Ready"

65 s ±15 s

Indication

According to group I of IEC 61243-1

Nominal voltage/Nominal frequency

The following three standard versions are available:

• Vn = 100 V – 300 V

• Vn = 300 V – 900 V

• Vn = 1000 V – 3000 V

See imprint on name plate, tolerance ± 10 %

16.7 — 60 Hz

Properties of the insulating rod Tested for leakage current of the insulating part with 1.2 x Ur for 1 min
Transportation length <1,100 mm (including catch hook probe)
Minimum length insulating element >520 mm
Power supply

Lithium cells, 6 years at approx. 10 ready cycles / day and 230 days / year